05.01.36 KAWEFLEX® SERVO 2XSL(St)CYK-J VFD TRAY ... UL/CSA 0,6/1 kV EMC 3+ UV DB, XLPE 90°C

Application

Increased oil-resistant control and power supply cables for use in cable trays or cable channels with frequency converter technology. For medium mechnical stresses,for fixed or flexible installation where free movement is required without tensile stress and without forced guidance systems, in dry, damp and wet interiors (incl. water-oil mixtures). For outdoor use and also for direct burial. TC-ER (Tray Cable - Exposed Run) approval open wiring between cable tray and industrial machines/plants acc. NEC 336.10(7)

Special Features

  • increased resistance to oil by special PVC outer sheath, largely resistant to acids and bases
  • max. perm. current carrying capacity at 30 ° C ambient temp.
  • direct burial
  • UV-res.acc.to EN 50396 & HD 605 A1; SUN RES acc.to UL 1581
  • low operating capacity, low coupling resistance
  • flexible at low temperatures up to -15 °C
  • TC-ER (Tray Cable - Exposed Run)
  • enables trouble-free operation of frequency converters through optimum EMC compliant shielding

Remarks

  • conform to RoHS, conform to 2014/35/EU-Guideline ("Low-Voltage Directive") CE
  • LABS-/silicone-free (during production)
  • conform to NFPA 79 2007 wiring norms and NEC 336.10 (7) acc. to NEC "National Electric Code"
  • Special versions, other dimensions, cross-sections, core and jacket colours are manufactured on request.

Structure & Specifications

conductor_material bare copper strand
conductor_class acc. to IEC 60228 cl. 5
insulation_material XLPE
wire_identification acc. to DIN VDE 0293-308 coloured cores with GNYE
twisting stranded in layers
shielding_total alu-lamin. polyester foil, metal side outside, cover. 100% under copper braid tinned
outersheath_material PVC
sheath_color black, RAL 9005
voltage_nominal Uo/U 0,6/1 kV (UL 1277: 600 V) - highest permissible operating voltage Single phase and three-phase: 700/1200 V, DC operation: 900/1800 V
voltage_test 6 kV
resistance_conductor nach IEC 60228 cl. 5
resistance_isolation min. 200 MΩ x km
carrying_capacity table in the datasheet
capacity table in the datasheet
bending_radius_smallest_fixed ≤ 12mm Ø: 5 x d; ≤ 20mm Ø: 7,5 x d; > 20mm Ø: 10 x d
bending_radius_smallest_moving ≤ 12mm Ø: 10 x d; ≤ 20mm Ø: 15 x d; > 20mm Ø: 20 x d
operating_temperature_fixed -40 °C / +90 °C
operating_temperature_moving -15 °C / +80 °C
conductor_temperature_max + 90 °C in operation; +250 °C in case of short-circuit
fire_behaviour self-extinguishing & flame-retardant acc.to IEC 60332-3-24 Cat. C, FT4/IEEE
oil_resistance UL OIL RES I
other_properties water-resistant acc. to UL wet approval 75°C
approbation UL/CSA: cULus 600 V / 90 °C - UL1277