Increased oil-resistant control and power supply cables for use in cable trays or cable channels with frequency converter technology. For medium mechnical stresses,for fixed or flexible installation where free movement is required without tensile stress and without forced guidance systems, in dry, damp and wet interiors (incl. water-oil mixtures). For outdoor use and also for direct burial. TC-ER (Tray Cable - Exposed Run) approval open wiring between cable tray and industrial machines/plants acc. NEC 336.10(7)
Special Features
increased resistance to oil by special PVC outer sheath, largely resistant to acids and bases
max. perm. current carrying capacity at 30 ° C ambient temp.
direct burial
UV-res.acc.to EN 50396 & HD 605 A1; SUN RES acc.to UL 1581
low operating capacity, low coupling resistance
flexible at low temperatures up to -15 °C
TC-ER (Tray Cable - Exposed Run)
enables trouble-free operation of frequency converters through optimum EMC compliant shielding
Remarks
conform to RoHS, conform to 2014/35/EU-Guideline ("Low-Voltage Directive") CE
LABS-/silicone-free (during production)
conform to NFPA 79 2007 wiring norms and NEC 336.10 (7) acc. to NEC "National Electric Code"
Special versions, other dimensions, cross-sections, core and jacket colours are manufactured on request.
Structure & Specifications
conductor_material
bare copper strand
conductor_class
acc. to IEC 60228 cl. 5
insulation_material
XLPE
wire_identification
acc. to DIN VDE 0293-308 coloured cores with GNYE
twisting
stranded in layers
shielding_total
alu-lamin. polyester foil, metal side outside, cover. 100% under copper braid tinned
outersheath_material
PVC
sheath_color
black, RAL 9005
voltage_nominal
Uo/U 0,6/1 kV (UL 1277: 600 V) - highest permissible operating voltage Single phase and three-phase: 700/1200 V, DC operation: 900/1800 V
voltage_test
6 kV
resistance_conductor
nach IEC 60228 cl. 5
resistance_isolation
min. 200 MΩ x km
carrying_capacity
table in the datasheet
capacity
table in the datasheet
bending_radius_smallest_fixed
≤ 12mm Ø: 5 x d; ≤ 20mm Ø: 7,5 x d; > 20mm Ø: 10 x d
bending_radius_smallest_moving
≤ 12mm Ø: 10 x d; ≤ 20mm Ø: 15 x d; > 20mm Ø: 20 x d
operating_temperature_fixed
-40 °C / +90 °C
operating_temperature_moving
-15 °C / +80 °C
conductor_temperature_max
+ 90 °C in operation; +250 °C in case of short-circuit