02.05.01 DATEX-CY Li2YCY (TP)
Application
Data transmission cable, control and connecting cable especially for cabling with high data transfer rates up to 10 Mb/s, for lossless data and signal transmission. For fixed laying and flexible applications with undefined cable routing and without tensile stress. Suitable for use in dry and humid rooms. Outdoor use only with UV-protection, no laying underground*.
Special Features
- twisted pairs
- largely resistant to acids, bases and specified types of oil
- LABS-/silicone-free (during production)
- recommended for EMC-applications
- suitable for maxi-termi-point applications by 7wire conductors <1 mm²
Remarks
- conform to RoHS
- conform to 2014/35/EU-Guideline ("Low-Voltage Directive") CE
- *: DATEX-CYv + UV LI2YCYv (TP) for indoor and outdoor use as well as laying directly underground
- We are pleased to produce special versions, other dimensions, core and jacket colours on request.
Structure & Specifications
conductor_material
bare copper strand
conductor_class
7 wired
insulation_material
PE
wire_identification
acc. to DIN 47100 different colours
twisting
pairs stranded in layers
shielding_total
copper braid tinned; coverage approx. 85%
outersheath_material
PVC
sheath_color
grey, RAL 7032 (CY) and black, RAL 9005 (CYv)
voltage_nominal
250 V
voltage_test
core/core: 2 kV; core/shield: 1 kV
resistance_conductor
loop: 0,22 mm² max. 186 Ω / km; 0,34 mm² max. 115 Ω / km; 0,50 mm² max. 78,4 Ω / km
resistance_isolation
min 5 GΩ x km
carrying_capacity
acc. to DIN VDE, s. Techn. Guidelines
capacity
max. 60 nF/km (from 4 pairs)
bending_radius_smallest_fixed
10 x d
bending_radius_smallest_moving
15 x d
operating_temperature_fixed
-30 °C / +80 °C
operating_temperature_moving
-5 °C / +70 °C
fire_behaviour
flame-retardant acc. to IEC 60332-1-2
standard
similar to DIN VDE 0812

Application
Data transmission cable, control and connecting cable especially for cabling with high data transfer rates up to 10 Mb/s, for lossless data and signal transmission. For fixed laying and flexible applications with undefined cable routing and without tensile stress. Suitable for use in dry and humid rooms. Outdoor use only with UV-protection, no laying underground*.
Special Features
- twisted pairs
- largely resistant to acids, bases and specified types of oil
- LABS-/silicone-free (during production)
- recommended for EMC-applications
- suitable for maxi-termi-point applications by 7wire conductors <1 mm²
Remarks
- conform to RoHS
- conform to 2014/35/EU-Guideline ("Low-Voltage Directive") CE
- *: DATEX-CYv + UV LI2YCYv (TP) for indoor and outdoor use as well as laying directly underground
- We are pleased to produce special versions, other dimensions, core and jacket colours on request.
Structure & Specifications
conductor_material | bare copper strand |
---|---|
conductor_class | 7 wired |
insulation_material | PE |
wire_identification | acc. to DIN 47100 different colours |
twisting | pairs stranded in layers |
shielding_total | copper braid tinned; coverage approx. 85% |
outersheath_material | PVC |
sheath_color | grey, RAL 7032 (CY) and black, RAL 9005 (CYv) |
voltage_nominal | 250 V |
voltage_test | core/core: 2 kV; core/shield: 1 kV |
resistance_conductor | loop: 0,22 mm² max. 186 Ω / km; 0,34 mm² max. 115 Ω / km; 0,50 mm² max. 78,4 Ω / km |
resistance_isolation | min 5 GΩ x km |
carrying_capacity | acc. to DIN VDE, s. Techn. Guidelines |
capacity | max. 60 nF/km (from 4 pairs) |
bending_radius_smallest_fixed | 10 x d |
bending_radius_smallest_moving | 15 x d |
operating_temperature_fixed | -30 °C / +80 °C |
operating_temperature_moving | -5 °C / +70 °C |
fire_behaviour | flame-retardant acc. to IEC 60332-1-2 |
standard | similar to DIN VDE 0812 |