Power, control and connecting cable for drive systems with frequency converter technology, for fixed laying and casually movement without tensile stress and without defined cable routing. Suitable for use in dry, humid and wet rooms. Outdoor use, but no laying underground.
Special Features
largely resistant to acids, bases and specified types of oil
max. perm. current carrying capacity at 30 ° C ambient temperature.
low operating capacity, low coupling resistance
with UV-resistant, halogen-free outer sheath
enables trouble-free operation of frequency converters through optimum EMC compliant shielding
low capacitance enables longer cable lengths between motor and frequency converter
increased power transmission with the same conductor cross-section compared to standard 2YSL(St)CY versions
Remarks
conform to 2014/35/EU-Guideline ("Low-Voltage Directive") CE
LABS-/silicone-free (during production)
Special versions, e.g. with 120 °C max. temperature at conductor, other dimensions, cross-sections, core and jacket colours are manufactured on request.
Structure & Specifications
conductor_material
bare copper strand
conductor_class
acc. to IEC 60228 cl. 5
insulation_material
XLPE
wire_identification
acc. to DIN VDE 0293-308 coloured cores with GNYE
twisting
stranded in layers
shielding_total
alu-lamin. polyester foil, metal side outside, cover. 100% under copper braid tinned
outersheath_material
halogen-free compound
sheath_color
black, RAL 9005
voltage_nominal
Uo/U 0,6/1 kV - highest permissible operating voltage Single phase and three-phase: 700/1200 V, DC operation: 900/1800 V
voltage_test
4 kV
resistance_conductor
acc. to IEC 60228 cl. 5
resistance_isolation
min. 200 MΩ x km
carrying_capacity
look at the table on the right side
capacity
look at the table on the right side
bending_radius_smallest_fixed
≤ 12mm Ø: 5 x d; ≤ 20mm Ø: 7,5 x d; > 20mm Ø: 10 x d
bending_radius_smallest_moving
≤ 12mm Ø: 10 x d; ≤ 20mm Ø: 15 x d; > 20mm Ø: 20 x d
operating_temperature_fixed
-40 °C / +80 °C
operating_temperature_moving
-15 °C / +70 °C
conductor_temperature_max
+ 90 °C in operation; +250 °C in case of short-circuit