Halogen-free and environmentally power, control and connecting cable in electrical facilities, in fire vulnerable areas and facilities with high concentration of people and property values, for fixed laying and flexible applications without tensile stress and without defined cable routing. Suitable for use in dry and humid rooms. Outdoor use only with UV-protection, no laying underground.
Special Features
LABS-free (during production)
FRNC (Flame Retardant, Non Corrosive)
LSF 0H ( Low smoke in fume, zero halogen)
recommended for EMC-applications
Remarks
conform to RoHS
conform to 2014/35/EU-Guideline ("Low-Voltage Directive") CE
also available: FLAME-JZ-HCHö FRNC with increased resistance to oil
We are pleased to produce special versions, other dimensions, core and jacket colours on request.
Structure & Specifications
conductor_material
bare copper strand
conductor_class
acc. to IEC 60228 cl. 5
insulation_material
special halogen-free compound
wire_identification
acc. to DIN VDE 0293 black cores with white numerals with GNYE from 3 cores
twisting
stranded in layers
shielding_total
copper braid tinned; coverage approx. 85 %
outersheath_material
special halogen-free compound
sheath_color
grey, RAL 7001
voltage_nominal
Uo/U: 300/500 V
voltage_test
3 kV
resistance_conductor
acc. to IEC 60228 cl. 5
resistance_isolation
min. 20 MΩ x km
carrying_capacity
acc. to DIN VDE, see technical Guidelines
bending_radius_smallest_fixed
6 x d
bending_radius_smallest_moving
15 x d
operating_temperature_fixed
-40 °C / +70 °C
operating_temperature_moving
- 5 °C / +70 °C
halogen_free
halogen-free acc. to IEC 60754-1
flue_gas_generation
acc. to IEC 61034-1 and IEC 61034-2
corrosiveness
acc. to IEC 60754-2
fire_behaviour
halogen-free and flame-retardant acc. to IEC 60332-1-2 and IEC 60332-3-24 Kat. C