09.01.01 LiYvz, H05V-K, H07V-K

Application

LiYvz as switching strand for wiring telecommunication units, electrical modules in devices as well as telecommunication facilities. H05V-K and H07V-K as single core for internal wiring of devices as well as protected laying within and on shiners. Laying within pipes on-wall and in-wall permitted for signal facilities.

Special Features

  • largely resistant to acids, bases and specified types of oil
  • LABS-/silicone-free (during production)
  • self-extinguishing and flame-retardant
  • no direct laying on pallets, in channels or trays (exceptional as potential compensation)
  • all usual standard colours available

Remarks

  • conform to RoHS
  • conform to 2014/35/EU-Guideline ("Low-Voltage Directive") CE
  • screened PVC-single core ELITRONIC®-CY LIYCY see chapter 02.01.02
  • We are pleased to produce special versions, other dimensions, core and jacket colours on request.

Structure & Specifications

conductor material LiYvz: copper strand tinned; H05V-K, H07V-K: bare copper strand
conductor class acc. to IEC 60228 class 5
core material PVC
core identification different colours
rated voltage H05V-K: 300/500 V; H07V-K: 450/750 V peak voltage LiYvz 500 V (0,14mm²), 900 V (0,25mm²-1,5mm²)
testing voltage LiYvz: 1,2 kV (0,14mm²), 2,5 kV (0,25mm²-1,5 mm²) H05V-K: 2 kV; H07V-K: 2,5 kV
resistance_conductor at +20 °C LiYvz acc. to VDE 0812; H05V-K and H07V-K acc. to IEC 60228
current carrying capacity acc. to. DIN VDE, see Technical Guidelines
min. bending radius fixed LIYvz: 10 x d // H05/07V-K: OD < 8,0 mm = 3xd; OD < 12,0 mm
min. bending radius moved 15 x d
operat. temp. fixed min/max -30 °C / +80 °C (HAR: +70 °C)
operat. temp. moved min/max -5 °C / +70 °C
burning behavior self-extinguishing & flame-retardant acc.to IEC 60332-1-2
standard LiYvz similar to VDE0812; H05/H07V-K: acc. to EN 50525-2-31 (IEC 60227-3)
approbation H05V-K and H07V-K: HAR

(PDF) information produit Télécharger le certificat