Heat and coldness resistant power, control and connecting cable in electrical facilities, for lossless data and signal transmission, for fixed laying and flexible applications without tensile stress and without defined cable routing. Suitable for use in dry, humid and wet rooms and outdoor use, no laying underground.
Special Features
largely resistant to acids, bases and specified types of oil
no flame conduction in case of fire, insulation integrity and low smoke density
resistant to ozone and humidty, weather-proofed
recommended for EMC-applications
above +100 °C and with exclusion of air, the mechanical properties of silicone cables will be reduced early, adequate ventilation should be ensured
Remarks
conform to RoHS
conform to 2014/35/EU-Guideline ("Low-Voltage Directive") CE
SIHF-SI+C: with inner sheath
We are pleased to produce special versions, other dimensions, core and jacket colours on request.
Structure & Specifications
conductor material
copper strand tinned
conductor class
acc. to IEC 60228 cl. 5
core material
silicone
core identification
up to 5 cores acc. to DIN VDE 0293-308 coloured cores; from 6 cores black cores with white numerals with or without GNYE
stranding
stranded in layers
shield
copper braid tinned; coverage appr. 85%
inner sheath material
SIHF-SI+C: silicone
inner sheath colour
redbrown
outer sheath
silicone
sheath colour
redbrown
rated voltage
Uo/U: 300/500 V
testing voltage
2 kV; core/shield: 1 kV
resistance_conductor
at +20 °C acc. to IEC 60228 cl. 5
resistance_isolation
min. 2,0 GΩ x km
current carrying capacity
acc. to DIN VDE, see Technical Guidelines
min. bending radius fixed
5 x d
min. bending radius moved
12 x d
operat. temp. fixed min/max
-60 °C / +180 °C; short-time: +200 °C
temp. at conductor
+180 °C
halogen_free
halogen-free acc. to IEC 60754-1
corrosiveness
acc. to IEC 60754-2
burning behavior
self-extinguishing and flame-retardant acc. to IEC 60332-1-2