03.10.04.01 DeviceNet™ 120 Ω Trunk & Drop UL/CSA

Application

As fieldbus cables for DeviceNet™ systems in the field of production automation for reliable data and energy transmission (e.g. between sensors, actuators and controllers), for fixed installation & flexible applications. DeviceNet™ is an Allen Bradley (Rockwell Automation) developed, based on proven CAN technology bus system. Standard acc. ODVA specifications  

Special Features

  • largely resistant to grease, coolant fluids and lubricants
  • oil-resistant: acc. to DIN EN 60811-2-1 (only mineral oil)
  • UV-resistant
  • optimized EMC compliant shielding
  • max. cable lengths for a bus segment at stated transmission rate as
    supply cable:
       Trunk - thick: 125 kbit/s-max.500m | 250 kbit/s-max.250m | 0,5 Mbit/s-max.100m                 
       Drop - thin   : 125 kbit/s-max.100m | 250 kbit/s-max.100m | 0,5 Mbit/s-max.100m

Remarks

  • conform to RoHS
  • conform to DESINA (violet)
  • conform to 2014/35/EU-Guideline ("Low-Voltage Directive") CE
  • LABS-/silicone-free (during production)
  • ODVA - Open DeviceNet Vendors Association

Structure & Specifications

conductor material copper strand tinned
conductor class 19-wired
core material BUScores: foamed PE, supply cores: PVC
core identification BUScores: bu, wh; supply cores: rd, bk
stranding cores twisted to pairs
shield pairs in aluminium clad foil, cover. 100%
shield copper braid tinned, with subjacent tinned drain wire
overall stranding pairs stranded in layers
outer sheath PVC
sheath colour violet RAL 4001 (VT) or grey RAL 7001 (GY)
rated voltage 300 V (not for high voltage purposee)
testing voltage 1,5 kV
resistance_loop max. 181,8 Ω/km - AWG24, max. 114,8 Ω/km - AWG22, max. 45,4 Ω/km - AWG18, max. 22,6 Ω/km - AWG15
capacity nom. 40 nF/km
surge_impedance 120 Ω +/- 12 Ω
min. bending radius fixed 7,5 x d
min. bending radius moved 15 x d
operat. temp. fixed min/max -40 °C / +80 °C
operat. temp. moved min/max -10 °C / +70 °C
burning behavior flame retardant acc. to IEC 60332-3-24(Cat.C),FT4
oil_resistance acc. to DIN EN 60811-2-1 (only mineral oil)
approbation UL/CSA - (Trunk Cable) cULus 300V, 75°C, CMG/PLTC/SunRes/OilRes & cURus 600V, 60°C | (Drop Cable) cULus 300V, 75°C, CMG/CL2/SunRes/OilRes & cURus 600V, 60°C

(PDF) information produit Télécharger le certificat