MULTIBUS - as fieldbus cable for use in a variety of fieldbus systems such as DIN measuring bus, BITBUS (IEEE 1118), Local Operating Network (LON) SUCOnet P, Modulink-P, P-VariNet, FIP ...
and
INTERBUS - as shielded remote bus cable (Type RBC) or installation remote bus with integrated power supply (type INBC) in the field of production automation, for fixed installation & flexible applications
Special Features
largely resistant to lubricants, coolants fluids and grease
oil-resistant: acc. to DIN EN 60811-2-1 (only mineral oil)
EMC compliant shielding
max. cable lengths for a bus segment acc.to PI at stated transmission rate:
MULTIBUS: 93,75kbit/s-max.1,2km | 187,5kbit/s-max.1km | 0,5Mbit/s-max.400m
1,5 Mbit/s-max.200m | 12,0 Mbit/s-max.100m
INTERBUS: 0,5Mbit/s-max.400m
Remarks
conform to RoHS
conform to DESINA (violet)
conform to 2014/35/EU-Guideline ("Low-Voltage Directive") CE
LABS-/silicone-free (during production)
Structure & Specifications
conductor material
bare copper strand
conductor class
0,22 mm²: 7-wired; 1,0 mm²: fine wired acc. to IEC 60228 cl. 5
core material
BUScores: Polyolefin, supply cores: PVC
core identification
BUScores: acc. to DIN 47100, supply cores: rd, bu, gnye
stranding
BUScores stranded to a pair
shield
copper braid tinned
overall stranding
(INBC) BUSelem. a. supply cores stranded
outer sheath
PVC
sheath colour
violet RAL 4001 (VT)
rated voltage
BUScores: 250 V (not for high voltage purposes); supply cores: 500 V