02.09.05 A-2Y(L)2Y St III Bd

Application

Outdoor telephone cable for railway station telecommunication, in business and industrial facilities, in telecommunication and IT-systems for lossless transmission of datas and signals. Suitable for fixed laying in dry and humid rooms, on-wall and in-wall, outdoor use and laying underground.

Special Features

  • shielded by plastic coated aluminium tape
  • quads stranded in bundles (St III Bd) with PE-outer sheath in layers
  • largely resistant to acids, bases, saline solution, water, alcohol, oil and petrol
  • free from lacquer damaging substances and silicone (during production)
  • A-2Y(L)2Y St III Bd: radially watertight, A-2YF(L)2Y St III Bd: radially & longitudinally watertight
  • UV-resistant outer sheath

Remarks

  • conform to RoHS
  • conform to 2006/95/EC-Guideline CE.
  • We are pleased to produce special versions, other dimensions, core and jacket colours on request.

Structure & Specifications

conductor material copper conductor blank
conductor class conductor-Ø 0,6 mm (0,28 mm²), conductor-Ø 0,8 mm (0,5 mm²)
core material PE
core identification acc. to VDE 0816: basic colours with black printed rings
stranding cores stranded to star-quads, bundles stranded in layers; A-2YF(L)2Y St III Bd: hollow spaces of cable strand filled with jelly filling
shield double-sided plastic coated aluminium tape
outer sheath PE
sheath colour black
rated voltage 225 V
testing voltage core/core: 500 V; core/shield: 2 kV
resistance_conductor loop: 0,6 max. 130 Ω / km ; 0,8 max 73,2 Ω / km
resistance_isolation min. 5 GΩ x km
current carrying capacity acc. to DIN VDE, s. Techn. Guidelines
capacity max. 52 nF/km
min. bending radius fixed 7,5 x d
min. bending radius moved 10 x d
operat. temp. fixed min/max +70 °C
operat. temp. moved min/max -20 °C / +50 °C
standard acc. to DIN VDE 0816

(PDF) information produit Télécharger le certificat