02.09.02 J-Y(St)Y Lg

Application

Installation cable with electrostatic shield for telecommunication and IT-systems for lossless transmission of datas and signals. Suitable for fixed laying in dry and humid rooms, on-wall and in-wall, outdoor use, no laying underground.

Special Features

  • shielded by plastic-clad aluminium foil
  • pairs stranded in layers (Lg)
  • largely resistant to acids, bases and usual oils
  • free from lacquer damaging substances and silicone (during production)
  • also available: JYY Bd. or J-Y(St)Y Lg BMK n x 2 x 0,8 mm as fire alarm cable with red outer sheath

Remarks

  • conform to RoHS
  • conform to 2006/95/EC-Guideline CE.
  • installation cables are not designed for high voltage purposes and are not suitable for laying underground
  • We are pleased to produce special versions, other dimensions, core and jacket colours on request.

Structure & Specifications

conductor material copper conductor blank
conductor class conductor-Ø 0,6 mm (0,28 mm²), conductor-Ø 0,8 mm (0,50 mm²)
core material PVC
core identification acc. to DIN VDE 0815 different colours
stranding pairs stranded in layers (2-pair-cable also possible as star quad)
shield plastic-clad aluminium foil with subjacent drain wire
outer sheath PVC
sheath colour grey, RAL 7032 (fire alarm cable: red)
rated voltage 300 V
testing voltage 800 V
resistance_conductor loop: 0,6 max. 130 Ω / km; 0,8 max. 73,2 Ω / km
resistance_isolation min. 100 MΩ x km
current carrying capacity acc. to DIN VDE, s. Techn. Guidelines
capacity max. 100 nF/km
min. bending radius fixed 7,5 x d
min. bending radius moved 10 x d
operat. temp. fixed min/max -30 °C / +70 °C
operat. temp. moved min/max - 5 °C / +50 °C
burning behavior self-extinguishing & flame-retardant acc.to IEC 60332-1
standard acc. to DIN VDE 0815

(PDF) information produit Télécharger le certificat